TJ1039 : Numerical Investigation of Heat Transfer in Power Cables in Southern Cities of Iraq (Specific Region) During Peak Consumption Periods in Summer to Prevent Fires and Power Outages
Thesis > Central Library of Shahrood University > Mechanical Engineering > MSc > 2026
Authors:
Abstarct:
Abstract
In the present research, heat transfer in overhead power lines of the type Aluminum Conductor Steel Reinforced (ACSR) in the southern cities of Iraq, with an emphasis on Najaf, during the peak summer consumption period, has been investigated using a numerical method and the finite element software COMSOL. The main objective was to prevent fires and power outages caused by excessive cable heating under critical weather conditions and high loads. First, the model was validated by comparing simulation results with data from a reputable reference article, achieving a very good در حالیکه در حضور باد مناسب، حتی در دمای محیط ۵۰ درجه، دمای هادی در حدود ۶۶ درجه و در محدودهی ایمن باقی میماند. همچنین بیشترین اثر خنککنندگی مربوط به زاویه باد عمود بر هادی (۹۰ درجه) است و در شرایط بدون باد، اختلاف دمای شعاعی بین هسته و سطح خارجی و در نتیجه تنشهای حرارتی بهطور محسوسی افزایش مییابد. یافتهها نشان میدهد که مدیریت پویای بار بر اساس پایش همزمان دمای محیط و سرعت و جهت باد میتواند از بروز حوادث گرمایشی، خاموشیهای گسترده و آتشسوزی در خطوط انتقال مناطق گرم و خشک جلوگیری کند.
کلیدواژگان: انتقال حرارت عددی، کابلهای برق ACSR، پیک مصرف تابستان، خنککاری با باد، جلوگیری از آتشسوزی
Abstract
In the present research, heat transfer in overhead power lines of the type Aluminum Conductor Steel Reinforced (ACSR) in the southern cities of Iraq, with an emphasis on Najaf, during the peak summer consumption period, has been investigated using a numerical method and the finite element software COMSOL. The main objective was to prevent fires and power outages caused by excessive cable heating under critical weather conditions and high loads. First, the model was validated by comparing simulation results with data from a reputable reference article, achieving a very good agreement (relative error less than 16.3%). Subsequently, by designing 31 different scenarios, including variations in ambient temperature (from -20 to +50 degrees Celsius), wind speed (0 to 12 m/s), wind angle ( -45 to 135 degrees), and electrical current (275 to 775 Amperes), the impact of each of these parameters on conductor temperature and radial temperature difference was analyzed. The results indicated that the current flow is the most significant source of heating, and wind speed is the most effective factor for natural cooling. The most critical condition was the combination of high current (650 Amperes), absence of wind, and moderate ambient temperature (20 degrees Celsius), which increased the core temperature to approximately 132 degrees Celsius, far exceeding the permissible limit of 80 degrees. Conversely, adequate wind, even at 50 degrees Celsius, could maintain the conductor temperature within a safe range (around 66 degrees Celsius). It was also found that a wind angle perpendicular to the conductor (90 degrees) has the greatest cooling effect, and the radial temperature difference between the core and the outer surface, which causes thermal stresses, significantly increases under windless conditions. The findings of this study suggest that dynamic load management baxsed on simultaneous monitoring of ambient temperature, wind speed, and direction can prevent thermal incidents. The results of this research can serve as a basis for developing operating guidelines for safe transmission lines in hot and arid regions, optimal network design considering prevailing wind direction, and prevention of widespread outages and fires during peak consumption periods.
Keywords:
#_Numerical heat transfer #ACSR power cables #summer peak consumption #wind cooling #fire prevention Keeping place: Central Library of Shahrood University